1000Vdc 315-1400A IR.50kA High Voltage Fast Acting Square Body Fuse 3#

  • Volts: 1000Vdc;
  • Amps: 315-1400A;
  • Interrupting Capacity:
    • Max 1000Vdc 50kA(or less);
    • Min BC ≥ 5In;
  • Time Constant: ≤ 5ms;
  • Class Type: aR;
, , , ,
SKU HCHVT1000-N-74E Category Tags , , , ,

Description

  • Higher voltage rating provides overall system efficiency using smaller, more economical conductors while meeting the need of higher voltage.
  • Up to ten times faster opening under high fault current conditions helps assure reliable protection of circuits and components.
  • Greater ampacity within sizing guidelines, excellent power of resisting voltaic impingement and environment temperature tolerance, excellent resistance to mechanical vibration and impact resistance.

CERTIFICATIONS

  • Refer To UL 248.1/UL 248.13
  • IEC 60269.1/IEC 60269.4 
  • UL, TUV
  • RoHS Compliant

Fuse Ratings

Connect Part No. Fuse Amps Size Average
@50KA/1000Vdc
Power
Loss (W)
Approvals
A²s
Melting
A²t
Clearing
100% UL TUV
Bolted HCHVT1000-315BN-74E 315A 3# 8,550 48,500 120
HCHVT1000-350BN-74E 350A 3# 12,150 68,640 125
HCHVT1000-400BN-74E 400A 3# 17,550 99,150 133
HCHVT1000-450BN-74E 450A 3# 27,900 157,600 145
HCHVT1000-500BN-74E 500A 3# 35,100 198,315 155
HCHVT1000-550BN-74E 550A 3# 49,500 279,675 163
HCHVT1000-630BN-74E 630A 3# 75,150 424,600 172
HCHVT1000-700BN-74E 700A 3# 103,500 625,700 185
HCHVT1000-800BN-74E 800A 3# 185,500 1,001,700 195
HCHVT1000-900BN-74E 900A 3# 274,500 1,454,850 203
HCHVT1000-1000BN-74E 1000A 3# 405,000 2,126,500 210
HCHVT1000-1100BN-74E 1100A 3# 517,500 2,696,500 225
* HCHVT1000-1250BN-74E * 1250A 3# 729,000 3,717,900 240
* HCHVT1000-1400BN-74E * 1400A 3# 1,125,000 5,512,500 265
  • If there are any requirements, please communicate with the original factory staff first.
  • I²t 1000Vdc 50kA,T:< 5ms;DC allows the maximum voltage:523V
  • Bolted: xxxBN-74E
  • without fuse indicator
Connect Part No. Fuse Amps Size Average
@50KA/1000Vdc
Power
Loss (W)
Approvals
A²s
Melting
A²t
Clearing
100% UL TUV
Din HCHVT1000-315UN-74E 315A 3# 8,550 48,500 120
HCHVT1000-350UN-74E 350A 3# 12,150 68,640 125
HCHVT1000-400UN-74E 400A 3# 17,550 99,150 133
HCHVT1000-450UN74E 450A 3# 27,900 157,600 145
HCHVT1000-500UN-74E 500A 3# 35,100 198,315 155
HCHVT1000-550UN-74E 550A 3# 49,500 279,675 163
HCHVT1000-630UN-74E 630A 3# 75,150 424,600 172
HCHVT1000-700UN-74E 700A 3# 103,500 625,700 185
HCHVT1000-800UN-74E 800A 3# 185,500 1,001,700 195
HCHVT1000-900UN-74E 900A 3# 274,500 1,454,850 203
HCHVT1000-1000UN-74E 1000A 3# 405,000 2,126,500 210
HCHVT1000-1100UN-74E 1100A 3# 517,500 2,696,500 225
* HCHVT1000-1250UN-74E * 1250A 3# 729,000 3,717,900 240
* HCHVT1000-1400UN-74E * 1400A 3# 1,125,000 5,512,500 265
  • UL:E533379(100-800A);TUV:J50590376 (100-800A)
  • Application process to be determined
  • If there are any requirements, please communicate with the original factory staff first.
  • Din: xxxUN-74E
  • without fuse indicator

Applications

  • ESS
  • Disconnector or Maintenance Safety Disconnect
  • Battery Pack Protection
  • Backup Protection For DC Relay

Downloads

Rated Products

TALK TO OUR EXPERT​

  • We will contact you within 12 hours
  • Don’t worry, we hate spam too!
  • 20

    Years of experience

    50+

    Countries & Areas

    500 +

    Customers

    30,000

    ㎡ Manufacturing Factory

    HIITIO logo full 300

    Talk to us now

    What products are you interested in?
    Just in case we can't get back to you in time

    Get Our Lastest Product Catalogue