1500V 50-630A Photovoltaic Semiconductor Fuse 2#

  • Volts: 1500Vdc
  • Amps: 50-630A
  • Breaking Capacity:
    • Max DC 50kA 1500Vdc
  • Class Type: gPV
  • Time Constant: ≤ 2±0.5 ms
,
SKU HCPVT1500-59ES Categories , Tag

Dimensions (mm)

Bolted xxB-59ES
Din xxxU-59ES

Description

  • It has a low I²t value
  • Strong current limiting capability
  • Low voltage drop
  • Excellent DC Performance
  • Capable of interrupting low overcurrents associated with faulted PV strings

Standards / Approvals

  • Refer To UL-248-19 / IEC 60269-1 / 6
  • Reach Declaration Available Upon Request
  • RoHS Compliant

Features & Benefits

  • The HCPVT series has been designed to meet the emerging circuit protection needs for 1500 volt photovoltaic systems.
  • These fuses provide full range protection for all potential overcurrent conditions that exist in PV applications.
  • Suitable for PV inverter protection and array combiner applications.

Product Characteristics

Item Test Condition/Methods Standard Performance
Time/Current 100% of current rating UL248-19 No Fusing;4 hours Min.
105% of current rating *UL UL-248.19 60 Minutes Min.
135% of current rating *UL UL-248.19; (61-600A) 120 Minutes Max.
150% of current rating *UL UL-248.19;(601-800A) 240 Minutes Max.
200% of current rating UL248-19;(61-100A) 8 Minutes Max.
UL248-19;(101-200A) 10 Minutes Max.
UL248-19;(201-400A) 12 Minutes Max.
UL248-19;(401-600A) 14 Minutes Max.
Endurance Test 100% of rating current for 4 hours and testing Temperature rise at the last 5min. UL248-19 ≤65K
  • Loading 100% Rated Current (1.0In A) for flowing, and it’s available to let current keep on flowing at least 4 hour without any melting.

Fuse Ratings

Connect Part No. Fuse Amps Average @50KA/1500Vdc Power Loss (W) Approvals
 A²s Melting A²t Clearing 100% 70% UL
Bolted

59ES

HCPVT1500-50B-59ES 50A 800 3,500 20 8 Pending
HCPVT1500-63B-59ES 63A 1,500 5,400 32 20 Pending
HCPVT1500-80B-59ES 80A 2,600 9,600 38 23 Pending
HCPVT1500-100B-59ES 100A 3,700 13,000 48 28 Pending
HCPVT1500-125B-59ES 125A 5,400 21,000 60 32 Pending
HCPVT1500-160B-59ES 160A 8,400 32,000 68 36 Pending
HCPVT1500-200B-59ES 200A 13,500 55,000 79 40 Pending
HCPVT1500-250B-59ES 250A 26,500 105,000 82 45 Pending
HCPVT1500-315B-59ES 315A 50,500 201,500 95 55 Pending
HCPVT1500-350B-59ES 350A 65,000 320,000 100 57 Pending
HCPVT1500-400B-59ES 400A 85,000 354,000 109 64 Pending
HCPVT1500-500B-59ES 500A 217,000 750,000 121 71 Pending
HCPVT1500-630B-59ES 630A 434,000 1,150,000 128 76 Pending
  • DC Cold Resistance are measured at <10% of rated current in ambient temperature of 25℃;
Connect Part No. Fuse Amps Average @50KA/1500Vdc Power Loss (W) Approvals
 A²s Melting A²t Clearing 100% 70% UL
Din

59ES

HCPVT1500-50U-59ES 50A 800 3,500 20 8 Pending
HCPVT1500-63U-59ES 63A 1,500 5,400 32 20 Pending
HCPVT1500-80U-59ES 80A 2,600 9,600 38 23 Pending
HCPVT1500-100U-59ES 100A 3,700 13,000 48 28 Pending
HCPVT1500-125U-59ES 125A 5,400 21,000 60 32 Pending
HCPVT1500-160U-59ES 160A 8,400 32,000 68 36 Pending
HCPVT1500-200U-59ES 200A 13,500 55,000 79 40 Pending
HCPVT1500-250U-59ES 250A 26,500 105,000 82 45 Pending
HCPVT1500-315U-59ES 315A 50,500 201,500 95 55 Pending
HCPVT1500-350U-59ES 350A 65,000 320,000 100 57 Pending
HCPVT1500-400U-59ES 400A 85,000 354,000 109 64 Pending
HCPVT1500-500U-59ES 500A 217,000 750,000 121 71 Pending
HCPVT1500-630U-59ES 630A 434,000 1,150,000 128 76 Pending
  • DC Cold Resistance are measured at <10% of rated current in ambient temperature of 25℃;

Applications

1500Vdc photovoltaic systems

Downloads

Related Products

TALK TO OUR EXPERT​

  • We will contact you within 12 hours
  • Don’t worry, we hate spam too!
  • 20

    Years of experience

    50+

    Countries & Areas

    500 +

    Customers

    30,000

    ㎡ Manufacturing Factory

    HIITIO logo full 300

    Talk to us now

    What products are you interested in?
    Just in case we can't get back to you in time

    CONTACT US

    Download Our Catalog

    Surge-Protection-Device-SPD-Catalog-Datasheet-PDF